EasyManuals Logo

Simplex 4010 Applications Manual

Simplex 4010
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
2-17
The Selective Bypass of NAC/Relay Circuits application allows a 24 Point I/O
switch to override the automatic operation of NACs and door holder relays (i.e.,
horns/strobes do not automatically turn ON and doors do not close when an
alarm condition occurs). This application also causes a Trouble to appear at the
panel to indicate that the bypass switch is active.
Use the PC Programmer application to program the following switch attributes.
Device Type. Select the GRAPHIN device type, which indicates that the
device being programmed is a 24 Point I/O switch.
Point Type. Any of the following switch point types can be used.
- OSWITCH. Specifies a two-position switch, supervised for open
circuits. Requires an EOL resistor.
- SSWITCH. Specifies a two-position switch, supervised for open and
short circuits. Requires EOL and current limited (up leg) resistors.
- TSWITCH. Three position (SPDT) switch, supervised for open
circuits. Requires EOL and current limited resistors.
- USWITCH. Two-position switch, unsupervised. Assumes that no
EOL or current limited resistor is used.
Mode. Select the ONOFF mode. This mode allows one position of the
switch to represent the ON state and another position to represent the OFF
state. Refer to Table 2-4 for information on which switch position is
equivalent to ON or OFF.
Reference Address. Select a user-defined digital pseudo point. A
Custom Control equation will monitor this point to determine if the signals
should be bypassed or not.
Table 2-4. Relationship between Point Status and ON/OFF State
Mode Point Type Point Status and Result
Limited* Turns point ON
USWITCH
Normal* Turns point OFF
Limited* Turns point ON
OSWITCH
Normal* Turns point OFF
Limited* Turns point ON
SSWITCH
Normal* Turns point OFF
Normal* Mode OFF
Limited* Turns Point ON
ONOFF – Programs the
switch to turn the
referenced point ON or
OFF. This mode is
typically used with a
2-position maintained or
a 3-position switch, and
is not intended to be
used with a 2-position
momentary switch.
TSWITCH
Short Indicates Short
* When the I/O points status is viewed from the LCD panel (using
Control/View Points menu selection), this is the state that appears when the
switch is in the ON or OFF position.
Continued on next page
Selective Bypass of NAC/Relay Circuits
Overview
Step 1. Define Switch
Attributes
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing

Related product manuals