EasyManua.ls Logo

Simplex 4010 - Pre-Signal Operation; Overview; Step 1. Define Nacs Device Type, Point Type, and Custom Label

Simplex 4010
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-2
This application monitors initiating devices and does the following:
Automatic Initiating Device Activation. Sounds a pre-alert, slow
march time tone when an automatic initiating device (for example, a smoke
or heat sensor) activates. This tone lasts for five minutes. After five
minutes, if no Alarm Silence has occurred, the tone converts to a temporal
general evacuation tone. The purpose of this is to alert system operators
that an automatic initiating device has triggered and allow them up to five
minutes to investigate the cause of the alarm.
Pull Station Activation. Sounds a temporal general evacuation tone,
for a duration of five minutes, when a pull station activates.
Note: Always consult the local AHJ to determine whether this type of
operation is allowed or not allowed.
The NACs used with the Pre-Signal application can be either the NACs located
on the panels SFIO board or the NACs located on a 4009 IDNet NAC extender.
Note: Class A QuickAlert cannot be used with pre-signal applications.
Use the PC Programmer to program the NACs with the device types and point
types listed in Table 4-1. When defining custom labels, make sure to use
descriptive labels, such as FLOOR1-VISUAL-CIRCUIT.
If necessary, refer to Chapter 7, Programming Points, of the 4010 PC
Programmer Installation and Programming Instructions (574-187) for
information on editing a points device type, point type, and custom label.
Table 4-1. NAC Device Types and Point Types
Option Explanation
SIGA
Use for Class A NAC. This type of NAC
contains multiple signal paths, allowing
circuit operation to continue if a single open
circuit occurs. This option requires
installation of a Class A NAC adapter card.
NAC
Device
Type
SIGB
Use for Class B NAC, which is a NAC
containing only a single circuit path.
QALERT
Use only for Class B QuickAlert NAC
appliances requiring Custom Control
(selective signaling).
NAC
Point
Type
SIGNAL
Use for either of the following:
- Non-QuickAlert (standard) NAC
appliances requiring Custom Control
(selective signaling).
Continued on next page
Pre-Signal Operation
Overview
Step 1. Define NACs Device
Type, Point Type, and Custom
Label
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Related product manuals