A-7
Alarm signal – On until Reset. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until a System
Reset is performed. Points assigned with this type operate on general alarm
(that is, when any point within the L1 General Alarm List goes into alarm).
Circuit Status LCD Display
System Status
ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
OFF AUTO TBLE Signal Circuit TROUBLE
Used only with visual notification appliances that must be ON until a System
Reset is performed. Points assigned with this type operate on general alarm
(that is, when any point within the L1 General Alarm List goes into alarm).
Circuit Status LCD Display
System Status
ON Visual ON
OFF Visual OFF
Visual CODING
Disable TBL Visual TROUBLE
Off Auto TBL Visual TROUBLE
Waterflow signal – On until Reset. A point with this type turns ON when any
point within L2, the Waterflow Alarm Monitor List, goes into alarm. Points
with this type turn OFF on System Reset.
Circuit Status LCD Display
System Status
ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
Off Auto TBL Visual TROUBLE
Continued on next page
Point Types, Continued
RSIGNAL
RVISUAL
RWATER