When  an  initiating  device  senses  a System  Supervisory  Condition  (tamper  valve  off  normal,  generator  status,  etc.), 
programmed  notification  appliances  and  the  tone-alert  sounds,  the  SYSTEM  SUPERVISORY  LED  on  the  interface 
panel  turns  ON  and  flashes,  the  city  circuit  may  be  activated  (if  required  by  local  codes),  and  various  programmed 
events  occur.  The  tone-alert  continues  sounding  until  the  condition  is acknowledged  or  cleared. 
When  the  4020  senses  a  malfunction  within  the  system  (loss  of  power,  hardware  failure,  etc.),  a Trouble  Condition 
is  announced  by  the  interface  panel.  The  tone-alert  sounds  steady,  the  SYSTEM  TROUBLE  LED  flashes  and 
various  programmed  events  occur.  The  tone-alert  continues  sounding  until  the  condition  is  acknowledged  or 
cleared. 
NOTE:  When  an  operator  interface  panel  key  is  referenced  within  this  manual,  it is  normally  shown  between  left 
and  right  arrows.  Examples  are  cACK>  and  <ALARM  SILENCE>. 
All  abnormal  conditions  must  be  acknowledged  by  pressing  the  cACK>  key  under  the  appropriate  flashing  LED. 
Notification  appliances  are  silenced  by  pressing  the  <ALARM  SILENCE>  key. 
NOTE:  When  you  press  the  <ALARM  SILENCE>  key,  the  ALARM  SILENCED  LED  turns  ON  steady. 
Depressing  the  <SYSTEM  RESET>  key  restores  the  system  to the  normal  operating  mode  if Fire  Alarm  Conditions 
have  been  acknowledged  and  restored.  Depressing  the  <PRIORITY  2 ALARM  RESET>  key  on  the  CONTROL  Key 
Panel  restores  the  system  to  normal  operation  if Priority  2 Alarm  Conditions  have  been  acknowledged  and  restored. 
(All  keys  on  the  CONTROL  Key  Panel  must  be  programmed  for  function.) 
The  tone-alert  may  be  programmed  to  sound  at  specified  time  intervals  to  serve  as  a  reminder  that  a trouble  still 
exists  within  the  system  (System  Trouble  Reminder). 
The  system  has  “re-sound”  capability.  If, after  silencing  the  signals,  the  system  detects  another  abnormal  condition, 
the  zone  with  the  abnormal  condition  is  indicated  on  the  interface  panel  alphanumeric  display,  the  appropriate 
indicator  again  flashes,  and  the  signals  again  sound. 
To provide  maximum  efficiency  in performing  primary  fire  alarm  functions,  an  interface  panel  access  door,  shown  in 
Figure  1, covers  all  keys  except  those  required  for  indication  and  interaction  for  emergency  situations.  (The  access 
door  must  be  opened  to  reset  Priority  2 Alarm  Conditions.) 
LOG  IN  PROCEDURE 
NOTE:  Various  functions  may  be  passcode  protected  to  prevent  access  by  unauthorized  personnel.  Passcodes 
are  provided  to  the  user  during  system  installation.  To  change  or  receive  additional  information  concerning 
your  passcodes,  contact  your  local  Simplex  Branch  Office. 
To Log  In,  perform  the  following  procedure. 
1.  Obtain  the  appropriate  passcode  information. 
2.  Open  the  interface  panel  access  door. 
3.  Press  the  <MENU>  key  on  the  Display/Action  keypad  on  the  right  side  of  the  interface  panel.  The 
alphanumeric  display  shows  the  following  message. 
I 
Press  <NEXT>  or  <PREVIOUS>  to  scroll 
Change  Access  Level? 
4.  Press  the  <ENTER>  key  on  the  Display/Action  keypad.  The  following  message  is displayed. 
I 
Fl=Login  F2=Logout 
CURRENT  ACCESS  LEVEL  =  1 
3 
Technical Manuals Online! - http://www.tech-man.com