Alarm  Silence  Software  Considerations 
The  following  software  functions  affect  ALARM  SILENCE  operation. 
l 
If a Coded  Input  Device  is activated,  the  <ALARM  SILENCE>  key  press  may  be  ignored  until  this  function 
has  completed  coding.  Notification  appliances  cannot  be  silenced  when  a coded  station  is in alarm.  However, 
the  flashing  LED  will  change  from  flashing  ON  to  steady  ON  when  the  <ALARM  ACK>  key  is  pushed.  The 
notification  appliances  silence  automatically  upon  coding  completion. 
l 
If the  Alarm  Silence  Inhibit  Function  is  activated  but  not  completed,  the  <ALARM  SILENCE>  key  press  is 
ignored.  The  message,  “ALARM  SILENCE  INHIBITED”,  displays  for  a short  time  to indicate  the  action  was  not 
taken.  The  message  “ALARM  SILENCE  NO  LONGER  INHIBITED”  displays  when  the  inhibit  function  times 
out.  If selected,  the  alarm  silence  inhibit  may  be  programmed  from  1 to  99  minutes.  When  selected,  signals 
cannot  be  silenced  until  the  programmed  time  has  elapsed.’ 
l 
If Waterflow/Sprinkler  Devices  are  activated,  notification  appliances  may  or may  not  be silenced  (depending 
on  local  code  requirements).  Usually,  a dedicated  bell  will  continue  to  sound  to  indicate  water  flow. 
l 
Some  visual  notification  appliances  may  continue  to  flash  until  the  system  is reset. 
SYSTEM  RESET  KEY 
The  <SYSTEM  RESET>  key  is  used  to  return  the  system  to  its  normal  state  after  a  Fire Alarm  Condition  has  been 
cleared.  When  the  <SYSTEM  RESET>  key  is pushed,  it causes  any  latched  circuits  to reset  automatically.  Also  reset 
are  initiating  devices,  relays  (including  the  city  relay),  notification  appliances,  and  all  LEDs  and  indicators  which  are 
programmed  to  reset  with  the  <SYSTEM  RESET>  key. The  message,  “SYSTEM  RESET  IN PROGRESS”,  displays 
when  the  <SYSTEM  RESET>  key  is  pressed.  When  the  Fire  Alarm  Condition  has  reset,  the  FIRE  ALARM  LED 
flashes,  and  the  system  requires  that  the  <ALARM  ACK>  key  be  pressed. 
When  the  <ALARM  ACK>  key  is pressed,  a message  should  be  displayed  that  is similar  to  the  one  shown  below. 
SYSTEM  IS  NORMAL 
8:37:13  MON  04-APR-94 
If a zone  stays  in alarm  during  the  reset  period,  the  message  “SYSTEM  RESET  IN PROGRESS”  is followed  by the 
message  shown  below. 
I 
ALARM  PRESENT,  SYSTEM  RESET  ABORTED 
When  the  “SYSTEM  RESET  ABORTED”  message  displays,  the  system  remains  in  an  alarm  state.  The  display 
indicates  the  total  number  of  alarms  present  in the  system  along  with  a  prompt  to  use  the  <ALARM  ACK>  key  to 
review  the  points.  These  points  do  not  require  acknowledgment.  The  ALARM  LED  remains  ON  to  indicate  that  a 
device  is still  in an  alarm  condition. 
If  the  system  does  not  reset,  and  the  display  still  shows  an  alarm  although  no  alarm  condition  exists,  read  the 
alphanumeric  display  on  the  interface  panel  to  determine  the  type  of  device  and  the  location  of the  device  in alarm. 
Follow  local  procedures  to  investigate  the  area  of  the  building  with  the  alarm.  Look  for  devices  still  in  alarm  (pull 
stations,  smoke  detectors,  etc.).  Most  devices  latch  until  they  are  reset,  either  by  the  system  or  manually. 
IF THE  ALARM  POINT  DOES  NOT  RESET 
If a device  does  not  reset,  you  may  choose  to  perform  the  Disable  Procedure  given  in the  following  paragraphs. 
13 
Technical Manuals Online! - http://www.tech-man.com