1. Unlock and open the enclosure door. The alphanumeric display on the interface panel shows the
supervisory condition.
I
**SUPERVISORY**
Press <ACK> to review.
FIRE = 0
PR12 = 0 SUPV = 1
TRBL = 0
I
2.
Press the <SUPV ACK> key under the flashing yellow LED. The alphanumeric display shows the area and
type of condition. The tone-alert silences and the yellow LED glows steady.
I
REVERE BASEMENT NORTH WING
ROOM 31
SPRINKLER MONITOR ABNORMAL
I
L
1
3. Read the alphanumeric display. Then, investigate the condition to determine its cause.
a. Restore or. replace the defective device (switch, wire, notification appliance, etc.) in accordance with
device instructions, or call Simplex to repair the system.
b. The supervisory condition automatically clears when the problem has been corrected.
c. After a delay, the alphanumeric display reads:
SYSTEM IS NORMAL
8:36:24
MON 04-APR-94
INDIVIDUAL ACKNOWLEDGE PANEL OPERATION DURING SUPERVISORY CONDITIONS
An INDIVIDUAL ACKNOWLEDGE of a System Supervisory Condition is accomplished in the following manner.
1. Unlock and open the enclosure door. The alphanumeric display shows a Supervisory Condition, such as
shown below.
I
**SUPERVISORY**
Press <ACK> to review.
FIRE = 0 PR12 = 0
SUPV = 1
TRBL = 0
I
2. Press the cSUPV ACK> key. Repeat this step and read the reports.
a. The tone-alert silences and the LED glows steady.
22
Technical Manuals Online! - http://www.tech-man.com
www.BevanSecurity.Com

Table of Contents

Other manuals for Simplex 4020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4020 and is the answer not in the manual?

Simplex 4020 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4020
DisplayLCD
Frequency50/60 Hz
Battery BackupYes
NAC Outputs4
Power120/240 VAC
Voltage120/240 VAC
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing
Communication ProtocolOptional