EasyManuals Logo

Simplex 4020 User Manual

Simplex 4020
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
IThere are two types of acknowledges for the 4020 system: Global Acknowledge and Individual Acknowledge. Each
acknowledge type operates with the Supervisory Condition in the following manner:
l
Global Acknowledge
- When Global Acknowledge is used on the 4020 system, a single key press of the
<SUPV ACK> key acknowledges all supervisory changes in the system. If status change information is
required, you may review this data (after a 30-second delay) by pressing the &UPV ACK> key and reading
the total number of supervisory changes on the alphanumeric display.
l
Individual Acknowledge (For NFPA 72 Proprietary Receiver Requirements) - If a supervisory condition has
been acknowledged with the cSUPV ACK> key and further unacknowledged conditions remain in the system,
the tone-alert continues to sound and the next status change is shown on the alphanumeric display. This
process repeats until all changes are acknowledged. When this occurs, the tone-alert silences and the highest
priority acknowledge change appears on the display.
24
Technical Manuals Online! - http://www.tech-man.com
www.BevanSecurity.Com

Table of Contents

Other manuals for Simplex 4020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4020 and is the answer not in the manual?

Simplex 4020 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4020
DisplayLCD
Frequency50/60 Hz
Battery BackupYes
NAC Outputs4
Power120/240 VAC
Voltage120/240 VAC
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing
Communication ProtocolOptional