Internal Power and Communications
1 TXD (Serial Communications Transmit
1 PI -1, P2-1, P2-5, JI-10, J2-10, J3-1
COMMON (Serial Communications Common)
RCV (Serial communications receive)
Pl-2, P2-2, P2-6, Jl -L, J2-L, J3-2
Pl-3, P2-3, P2-7, Jl-11 , J2-11, J3-3
CODE (coded signal bus line)
8C (8-volt common, OV)
+8V (+8-volt system power)
24C (24-volt common, OV)
+24V (+24-volt system power)
PI -4, P2-4, P2-8, Jl -M, J2-M, J3-4
Pl-5, Pl-6, P3-1 ,P3-5, JI-12, J3-6, J2-12, J3-5
PI-7, P3-2, P3-6, Jl-N, J2-N, J3-7
PI -8, PI -9, P3-3, P3-7, Jl-13, J3-9, J2-13, J3-8
Pl-10, P3-4, P3-8, Jl-P, J2-P, J3-10
P4
Local Energy P4-2, -5, -7, -9, -12, -13
Reverse Polarity P4-1, -3, -7, -8, -12
Shunt P4-1, -5, -13
I Radio
[ P4-4, -6, -13
I
Form C
j P4-13
P4
/
- \ 1
1 1
1
4 ““V”“VV
\ I
ti2
j2 til
P3
Figure 8
565-213 UT Master Motherboard
MASTER POWER SUPPLY BOARD (562-808)
NOTE:
The 5-Amp Master Power Supply Board uses the 478-282 Transformer. The 8-Amp Master Power Supply
Board uses two transformers:
l
Main Transformer (478-291)
l
Battery Transformer (478-201).
The Master Power Supply maintains and monitors the charge on standby batteries. It constantly monitors for the
following troubles:
l
Grounded circuitry (Earth Trouble)
l
Electrical brownout (low input AC power)
l
Low or disconnected batteries
l
Secondary AC power failure
l
Blown fused outputs
l
Expansion Power Supply troubles.
In event of a failure in any of the above, LED1 on the Power Supply Board lights, the system piezo (tone alert)
sounds, and the trouble condition is displayed on the Operator Interface Panel LCD (Liquid Crystal Display).
13
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100 and is the answer not in the manual?

Simplex 4100 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4100
Network CapabilityYes
AddressableYes
Power Supply120/240 VAC, 50/60 Hz
DisplayLCD
Annunciator SupportYes
Battery BackupYes
Releasing CapabilityYes
Max DevicesDepends on configuration
Max Notification Appliance Circuits (NAC)Varies with configuration
Max Releasing CircuitsVaries with configuration
Max Remote AnnunciatorsVaries with configuration
Communication PortsMultiple
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
NAC Outputs4 (expandable)
NetworkingYes