J
SWI-2 through SW1 -8 = Card address select switches (SW1 -2 = MSB, SW1 -8 = LSB).
LED1
SW1
LED2
LED3 LED4
1
RUI ASSY 565-217A 2
Figure 30
Remote Unit Interface Card
DECODER MODULE (565270)
Features and Functions
Provide an interface to mechanical and electronic coded initiating devices.
Component Locations and Functions (Figure 31)
LED1
Lights during initialization until communications are
established with the 4100 Master and whenever
communications are lost with the Master.
16 character x 2 line LCD that is used in programming the Decoder Module. Potentiometer Rl is used to adjust the
LCD contrast for best viewing.
Switches
SW1
Up = PROGRAM mode (allows codes of the stations connected to the Decoder to be entered.
While in this mode, alarm reporting is disabled, and a MAPNET Communications Failure
message is indicated at the 4100 front panel)
Down = NORMAL mode (enables Alarm Decoding and reporting)
SW2-SW7 Push button switches which are used in programming the Decoder
SW2 = Selects programming mode
SW3 = Move Left
50
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100 and is the answer not in the manual?

Simplex 4100 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4100
Network CapabilityYes
AddressableYes
Power Supply120/240 VAC, 50/60 Hz
DisplayLCD
Annunciator SupportYes
Battery BackupYes
Releasing CapabilityYes
Max DevicesDepends on configuration
Max Notification Appliance Circuits (NAC)Varies with configuration
Max Releasing CircuitsVaries with configuration
Max Remote AnnunciatorsVaries with configuration
Communication PortsMultiple
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
NAC Outputs4 (expandable)
NetworkingYes

Related product manuals