25WATT AMPLIFIER
(562-905j(FIGURE 49)
NOTE:
Adjust R24 to obtain a 27.5V RMS signal between P9-1 and P9-2.
*Turning Potentiometer R24 clockwise increases signal.
R24
P9
Figure 49
25-Watt Amplifier Component Locations
loo-WATT AMPLIFIER
(562-907)(FIGURE 50)
NOTE:
While reading the signal between Pins P9-1 and P9-2, adjust Rl to obtain a 27.5V RMS signal (if dealing
with a 562-009 amplifier) or a 73V RMS signal (if dealing with a 562-063 amplifier).
*Turn Potentiometer Rl counterclockwise slow/y to increase the signal.
83
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100 and is the answer not in the manual?

Simplex 4100 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4100
Network CapabilityYes
AddressableYes
Power Supply120/240 VAC, 50/60 Hz
DisplayLCD
Annunciator SupportYes
Battery BackupYes
Releasing CapabilityYes
Max DevicesDepends on configuration
Max Notification Appliance Circuits (NAC)Varies with configuration
Max Releasing CircuitsVaries with configuration
Max Remote AnnunciatorsVaries with configuration
Communication PortsMultiple
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
NAC Outputs4 (expandable)
NetworkingYes

Related product manuals