Identical in function to Switch SW1 in an El-Zone Monitor Card.
JumDers
NOTE:
The following jumpers are zero-ohm resistors.
CARD TYPE
JWI
1 Channel, 2 Points, Style Y OUT
1 Channel, 2 Points, Style Z IN
1 Channel, 6 Points, Style Y OUT
1 Channel, 6 Points, Style Z IN
2 Channel, 4 Points, Style Y OUT
2 Channel, 4 Points, Style Z IN
4 Channel, 2 Points, Style Y OUT
4 Channel, 2 Points, Style Z IN
JW2 / JW3
OUT IN
OUT IN
OUT OUT
OUT OUT
IN N/A
OUT N/A
IN N/A
IN N/A
JW4
OUT
OUT
OUT
OUT
N/A
N/A
N/A
N/A
JW5 JW6 JW7
N/A
N/A N/A
N/A N/A N/A
N/A
N/A N/A
“”
N/A 1 OUT 1 OUT 1
NOTE:
A Style Z signal card can be converted to Style Y operation by changing its jumper settings, but not vice
versa.
Connectors
NOTE:
See the 841-784 Field Wiring Diagram.
Pl = Fits into Socket J2 on the motherboard.
P2, P3, P4 and P5 = 6-pin 24VDC signal power, phone input or audio input connectors, each capable of
accommodating two of the following harnesses.
l
For 24VDC signal power = 733-523 harness (49)
733-578 harness (24)
l
For audio or phone inputs
i
733-579 harness (43)
733-580 harness (76)
l
Input harnesses must connect to pins 1, 2 and 3. Output harnesses (if used) must connect to pins 4, 5 and 6.
IMPORTANT: Check harness connections before applying power.
AN IMPROPER CONNECTION MAY CAUSE SYSTEM DAMAGE!
31
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100 and is the answer not in the manual?

Simplex 4100 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4100
Network CapabilityYes
AddressableYes
Power Supply120/240 VAC, 50/60 Hz
DisplayLCD
Annunciator SupportYes
Battery BackupYes
Releasing CapabilityYes
Max DevicesDepends on configuration
Max Notification Appliance Circuits (NAC)Varies with configuration
Max Releasing CircuitsVaries with configuration
Max Remote AnnunciatorsVaries with configuration
Communication PortsMultiple
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
NAC Outputs4 (expandable)
NetworkingYes