Communication
Problem Cause and corrective measure
Communication with at least one de-
vice is disturbed.
There may be a disturbance in the device.
Corrective measures:
Check the Cluster Controller event log (see
Section9.1, page51).
Refer to the device documentation.
The ClusterController may not be connected to the de-
vice.
Corrective measures:
Ensure that the network cables are correctly
connected (see the ClusterController installation
manual).
Check whether the network components, network
cables or connectors are defective or damaged.
Replace defective or damaged network components,
network cables or connectors.
Check whether the network settings of the individual
network components are correct. Adapt the network
settings if required.
If the problem persists, contact the network
administrator.
Problem Cause and corrective measure
Communication with all devices is dis-
turbed.
There is a problem in the LAN.
Corrective measures:
Ensure that the network cables are correctly
connected (see the ClusterController installation
manual).
Check whether the network components, network
cables or connectors are defective or damaged.
Replace defective or damaged network components,
network cables or connectors.
Check whether the network settings of the individual
network components are correct. Adapt the network
settings if required.
Restart the ClusterController. Disconnect the
ClusterController from the voltage supply and
reconnect it to the voltage supply.
If the problem persists, contact the network
administrator.
18 Troubleshooting
SMA Solar Technology AG
User ManualClusterController-BA-en-15102

Table of Contents

Other manuals for SMA CLUSTER CONTROLLER

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMA CLUSTER CONTROLLER and is the answer not in the manual?

SMA CLUSTER CONTROLLER Specifications

General IconGeneral
Data LoggingYes
DisplayLCD
Power Supply24 V DC
Remote MonitoringYes
Protection ClassIP20
Communication InterfacesEthernet
Product TypeController
ManufacturerSMA

Related product manuals