ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 30 of 83
When controller detects the Coolant Level Low Shutdown input is active,
it will send shutdown signal and the corresponding alarm information will
be displayed on the LCD.
When controller receives engine shutdown alarm signals via J1939, it will
send shutdown signal and corresponding alarm information will be
displayed on the LCD.
When engine is firing, controller receives no data via J1939, it will send
shutdown signal and the corresponding alarm information will be
displayed on the LCD.
If it is enabled, when controller detects the coolant temperature
transferred by EFI engine is higher than the maximum limit of preset
value, it will send shutdown signal and the corresponding alarm
information will be displayed on the LCD.
If it is enabled, when controller detects the oil pressure transferred by EFI
engine is lower than the minimum limit of preset value, it will send
shutdown signal and the corresponding alarm information will be
displayed on the LCD.
Low Voltage Start
Charging Timeout
After low starter battery voltage start is active, if charging time exceeds
the pre-set max. charging time, t will send shutdown signal and the
corresponding alarm information will be displayed on the LCD.
NOTE: The shutdown alarm types of input ports are active only when they are configured by users.
NOTE: for ECU warning and shutdown alarm illustration, if detailed alarm content displayed, users can check
engine according to the details; otherwise, users can check engine manual based on the SPN alarm codes to achieve
the information.