ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 35 of 83
7.2 GENERIC PARAMETER SETTINGS
Table 19 Generic Parameter Settings
Category
Parameters
Range
Default
Description
Timers
Start Delay
(0~3600)s
5
It is time from remote start
signal is active to genset
started.
Stop Delay
(0~3600)s
5
It is time from remote start
signal is deactivated to
genset stopped.
Preheat Delay
(0~3600)s
0
It is pre-energized time of
glow plug before starter is
powered up.
Cranking Time
(1~60)s
5
It is starter each power-up
time.
Crank Rest Time
(3~60)s
10
It is waiting time to
repower-up when the
engine starts fail.
Safety On Time
(0~3600)s
10
During this time, alarms
including low oil pressure,
high temperature, under
speed, gen under
frequency, gen under
voltage, and fail to charge
are deactivated.
Start Idle Time
(0~3600)s
10
It is genset idle running time
while starting up.
Warming Up Time
(0~3600)s
30
After generator entering into
high speed running, it is
warming up time before
ramp-on load.
Cooling Time
(0~36000)s
60
After genset ramp-off load,
it is cooling time before
genset stop.
Stop Idle Time
(0~3600)s
10
It is genset idle running time
while stopping.
ETS Hold Time
(0~3600)s
20
It is electromagnet
power-down time when to
sop.
Wait Stop Time
(0~3600)s
30
When ETS Solenoid Hold
time set as 0, it is time
needed from idle delay
expired to genset stop
completely; when ETS
Solenoid Hold time not set