shutdown event seleCtion
• UPS on battery (AC Failed)
• Battery Low
• Battery Level
• Imminent Stop
• UPS Overload
• Temperature Alarm
• On Bypass
• Weekly Schedule – activate the Weekly schedule page
• Special Day – activate the Special Schedule page
Additional events if EMD device present:
• EMD Temperature
• EMD Humidity
• EMD Alarm-1
• EMD Alarm-2
shutdown test proCedure
Net Vision allows you to simulate an AC fail event. After test validation the Shutdown procedure
starts, with the settings of ‘AC failed’ event.
The AC Failed simulation is disabled if the AC Failed Shutdown action is disabled.
Net Vision sends the notication and the shutdown command to the server.
At the end of the procedure, after sending the shutdown command. Net Vision waits around 2
minutes before sending a shutdown cancel command. This command permits the agent to re-
cover normal UPS status. The agent is then ready for the shutdown procedure again.
During the test, the button is disabled and switches to ‘enabled’ when the ‘shutdown cancel’
command is sent to servers.
WARNING!
If the Warning period = 0, the server shutdown command is sent immediately.