NET-VISION 7 - SOCOMEC
appendix: net vision 7 mib file oid desCription
upsIdent(1) No. Variables
.1.3.6.1.4.1.4555.1.1.7.1.1
1 upsIdentModel
2 upsIdentSerialNumber
3 upsIdentUserRef
4 upsIdentUserLocation
5 upsIdentAgentSoftwareVersion
upsBattery (2) No. Variables Values
.1.3.6.1.4.1.4555.1.1.7.1.2
1 upsBatteryStatus
unknown(1).
batteryNormal(2).
batteryCharging(3).
batteryTest(4).
batteryDischarging(5).
batteryLow(6).
batteryDepleted(7).
batteryFailure(8).
batteryDisconnected(9)
2 upsSecondsOnBattery Seconds
3 upsEstimatedMinutesRemaining Minutes
4 upsEstimatedChargeRemaining %
5 upsBatteryVoltage Format ###.# V
6 upsBatteryTemperature Format ##.# °C (*)
upsInput(3) No. Variables Values
.1.3.6.1.4.1.4555.1.1.7.1.3
1 upsInputNumLines 3 for 3 phase UPS
2 upsInputFrequency Format ##.# Hz
3 upsInputTable/upsInputEntry/
3.1.1 upsInputLineIndex
3.1.2 upsInputVoltage ###.# V
3.1.3 upsInputCurrent ###.# A (*)
3.1.4 upsInputVoltageMax ###.# V
3.1.5 upsInputVoltageMin ###.# V
General rule: In case measurements not managed by UPS the related IOD value is set at -1
or 65535.