NET-VISION 7 - SOCOMEC
upsOutput(4) No. Variables Values
.1.3.6.1.4.1.4555.1.1.7.1.4
1 upsOutputSource
Unknown (1).
onMaintenanceBy-
pass(2).
onInverter(3).
normalMode(4).
ecoMode(5).
onBypass(6).
standby(7).
upsOff(8).
2 upsOutputFrequency Format ##.# Hz
3 upsOutputNumLines 3 for 3 phase UPS
4 upsOutputTable/upsOutputEntry/
4.1.1 upsOutputLineIndex
4.1.2 upsOutputVoltage ###.# V
4.1.3 upsOutputCurrent ###.# A
4.1.4 upsOutputPercentLoad ### %
4.1.5 upsOutputKva ###.# kVA (*)
4.1.6 upsOutputKw ###.# kW (*)
(*) measurements are set to a value of -1 if the measurement is not managed
upsBypass(5) No. Variables Values
.1.3.6.1.4.1.4555.1.1.7.1.5
1 upsBypassFrequency Format ##.# Hz
2 upsBypassNumLines 3 for 3 phase UPS
3 upsBypassTable/upsBypassEntry/
3.1 upsBypassLineIndex
3.2 upsBypassVoltage ###.# V
3.3 upsBypassCurrent ###.# A (*)