Errors and Troubleshooting
SolarEdge Installation Guide – MAN-01-00002-1.6
106
Error #
LCD
Description Troubleshooting
32 AC Voltage
Too Low
Grid Voltage is below
the limit permitted in
this country.
Consult the grid operator.
If you are permitted by the local
authorities, then use the SolarEdge
Configuration Tool to change the
settings. Refer to the SolarEdge
Installation Tool User Guide for
more detail.
33 AC Voltage
Too High
Grid voltage is above
the limit permitted in
Handle this in the same manner as
error 31.
34
High
the limit permitted in
this country.
Consult the grid operator.
If you are permitted by the local
authorities, then use the SolarEdge
Configuration Tool to change the
settings. Refer to the SolarEdge
Installation Tool User Guide for
35
Low
the limit permitted in
this country.
Consult the grid operator.
If you are permitted by the local
authorities, then use the SolarEdge
Configuration Tool to change the
settings. Refer to the SolarEdge
Installation Tool User Guide for
more detail.
36 DC Injection DC feed detected on
If the problem persists, contact
SolarEdge support.
37-38 Ground
Current -
RCD
Ground current surge.
The internal hardware
that measures ground
fault has measured
substantially high
Handle this in the same manner as error
10.
40 Islanding AC grid voltage
malfunctions. The
inverter has shut off
due to islanding.
When AC voltage returns the inverter
should restart after some time (time
depends on country grid connection
codes)
If the problem persists, then consult with
the grid operator whether frequent AC
disruptions have occurred at the site.