Technical Specifications
SolarEdge Installation Guide MAN-01-00002-1.6
109
SE3000US
SE3800US
SE5000US
SE6000US
SE7000US
Maximum Output Overcurrent
Protection
40 A
Output Power Factor 1
GFDI 1 A
Utility Monitoring, Islanding
Protection, Country Configurable
Thresholds
Yes
Input
Recommended Max. DC Power* (STC)
3750
4750
6250
7500
8750
W
Transformer-less, Ungrounded Yes
Maximum Input Voltage
500
Vdc
Nominal DC Input Voltage 325 @ 208V / 350 @ 240V / 400 @ 277V Vdc
Maximum Input Current
10
12.5
16
18
18.5
Adc
Maximum Input Short Circuit Current 30 Adc
Maximum Input Source Back-feed
Current
0 A
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection
600 kΩ Sensitivity
Maximum Inverter Efficiency 97.8 97.7 98.3 98.3 98.3 %
CEC Weighted Efficiency 97.5 97 @
208V /
97.5 @
240V
97 @ 208V / 97.5 @ 240V / 98 @277V %
Nighttime Power Consumption < 2.5 W
Additional Features
Supported Communication Interfaces RS485, RS232, Ethernet, ZigBee (optional)