114 V 1.3 © Studer-Innotec SA next3 Tech manual
o Cmd entry: The relay is closed in association with a command entry.
o Error/Warning: relay is activated when there is an alarm in the system.
o Advanced combinations of conditions: Custom logic: (to come with future software
update!). Custom logic allows multiple combinations of conditions and is for
advanced users. All the settings are accessible at level 3 only (listing).
The detailed levels are chosen by default to fit in most situations, we then advice to only activate
one function without changing detailed parameters.
Most of the above pre-set signals can be temporally processed using a temporal restriction.
8.7.4.1 Battery voltage
Activation and deactivation of the AC-Flex load contact in function of the battery voltage. The
parameters to setup this function are:
Activation threshold voltage [V]
If the battery voltage exceeds this value, the relay is
activated.
Deactivation threshold voltage [V]
If the battery voltage exceeds this value, the relay is
deactivated.
These 2 values are the boundaries of a hysteresis function.
8.7.4.2 Battery SOC
Activation and deactivation of the AC-Flex load contact in function of the state of charge of the
battery connected to the device. The parameters to setup this function are:
Activation threshold SOC [%]
If the battery SOC exceeds this value, the relay is
activated.
Deactivation threshold SOC [%]
If the battery SOC exceeds this value, the relay is
deactivated.
These 2 values are the boundaries of a hysteresis function.
8.7.4.3 Battery temperature
Activation and deactivation of the AC-Flex load contact in function of the temperature of the
battery connected to the device. The parameters to setup this function are:
Activation threshold temperature [°C]
If the battery temperature exceeds this value, the
relay is activated.
Deactivation threshold temperature [°C]
If the battery temperature exceeds this value, the
relay is deactivated.
These 2 values are the boundaries of a hysteresis function.
8.7.4.4 Battery charging state
AC-Flex load relay is energized when the current battery charging state corresponds to one of the
selected states in the following list:
None
Bulk
Reduced Floating
Floating