147
Parameters SH8.0RT SH10RT
Frequency range 50 Hz / 60 Hz
Total hamonic factor output
voltage(Linear load)
2%
Switch time to emergency
mode
< 20 ms
Rated output power
8000 W / 8000 VA
10000 W / 10000 VA
9999 W / 9999 VA for
Australia
Peak output power ***
12000 W / 12000 VA,5min
Peak output power on single
phase ****
2700 VA (≥128kWh) 3400 VA (≥128kWh)
Rated output current for
backup load during on grid
mode
3 x 18.5 A
* Depending on the connected battery.
** Germany is available for 2 inverters parallel in maximum if no ripple control is used in
system.
*** Can be reached only if PV and battery power is sufficient.Detail compatibility for backup
under off-grid scenario can be referred to the user manual.
**** Peak power only for Resistive loads. Detail refer to SHRT backup output power
document.
Parameters SH5.0RT-20 SH6.0RT-20
PV Input
Recommended max. PV in-
put power
7500 W 9000 W
Max. PV input voltage
1000 V 1000 V
Min. PV input voltage / Start-
up voltage
150 V / 180 V 200 V / 250 V
Rated input voltage
600 V 600 V
MPP voltage range
150 V - 950 V 200 V - 950 V
MPP voltage range for rated
power
210 V - 850 V 250 V - 850 V
No. of MPPTs 2
Max. number of PV strings
per MPPT
1 / 1
Max. PV input current 27 A (13.5 A / 13.5 A)
Max. current for input
connector
30 A
User Manual 11 Appendix