For SH10RT/SH10RT-20, if two PV strings are paralleled externally, the paralleled strings
can be connected to PV2 or PV3 only, and the other one cannot be used to connect other
PV strings.
Prior to connecting the inverter to PV inputs, the following electrical specifications must be
met simultaneously:
Model Open-circuit Voltage Limit Max. current for Input
Connector
SH5.0RT/SH5.0RT-20
1000 V 30 A
SH6.0RT/SH6.0RT-20
SH8.0RT/SH8.0RT-20
SH10RT/SH10RT-20
6.6.2 Assembling the PV Connectors
High voltage may be present in the inverter!
• Ensure all cables are voltage-free before performing electrical operations.
• Do not connect the DC switch and AC circuit breaker before finishing electrical
connection.
To ensure IP65 protection, use only the supplied connector.
step 1 Strip the insulation from each DC cable by 7 mm–8 mm.