EasyManua.ls Logo

Sungrow SH10RT - Page 28

Sungrow SH10RT
166 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
figure 2-4 Parallel PV ESS
(A) Master (B) Slave 1 (C) Slave 2
(D) GRID (E) BACK-UP (F) RS485
Only the hybrid GRID terminals can be connected in parallel, the BACK-UP termi-
nals and the battery terminals cannot be connected together. Each hybrid must
have its own BACK-UP loads. The Backup loads of each inverter should not ex-
ceed its nominal power.
Refer to "6.7.3 RS485 Connection" for the cable connection.
In an on-grid parallel system, the master inverter collects information from Smart Energy
Meter and slave inverter and performs the energy management including:
Feed-in power control.
Battery charge / discharge
Maximum power limitation
The following settings are required for the inverter parallel function.
Feed-in power control. The feed-in power control function refers to "8.5.1 Feed-in Limita-
tion". The PV installation power of the master inverter is the total installation power of the
system, the slave inverters do not need to set the feed-in power.
2 Product Description User Manual

Table of Contents

Other manuals for Sungrow SH10RT

Related product manuals