EasyManua.ls Logo

Sungrow SH3K6 - Energy Meter; Quality Assurance

Sungrow SH3K6
118 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12 Appendix V: Technical Data User Manual
106
Mechanical Data
Dimensions (W x H x D)
457 mm x 515 mm x 170 mm
Mounting method
Wall-mounting bracket
Weight
22 kg
For the Q(P) mode in Italy, when the PF is 0.90 and the active power is 100 %,
(1) SH3K6: the maximum AC output apparent power to grid is 4000 VA.
(2) SH4K6: the maximum AC output apparent power to grid is 5110 VA.
12.2 Energy Meter
Item
Single-phase
Three-phase
Nominal voltage
240 Vac
3 x 230 Vac / 400 Vac
Input voltage range
180 Vac...286 Vac
3 x 180 / 311 Vac...
3 x 268 / 464 Vac
Power consumption
< 2 W (10 VA)
< 2 W (10 VA)
Max. operating current
100 A
3 x 10 (80) A
Grid frequency
50 Hz
Measurement accuracy
Class I
Interface and communication
RS485
Ingress protection rating
IP20
Operating ambient
temperature
-25℃...+75℃
-25℃...+55℃
Relative humidity
0...95 % (no condensation)
Mounting method
35 mm DIN-rail
Dimensions (W x H x D)
18 x 117 x 65 (mm)
127 x 70 x 89 (mm)
Weight
0.2 kg
0.35 kg
12.3 Quality Assurance
When product faults occur during the warranty period, SUNGROW will provide
free service or replace the product with a new one.
Evidence
During the warranty period, the customer shall provide the product purchase
invoice and date. In addition, the trademark on the product shall be undamaged
and legible. Otherwise, SUNGROW has the right to refuse to honor the quality
guarantee.
Conditions
After replacement, unqualified products shall be processed by SUNGROW.