User Manual 10 Appendix II: LCD Operation
91
Refer to the following table for the error type explanations.
Fault Type
Explanation
GRID
Grid faults (AC side)
PV
PV faults (DC side)
SYS
System faults (inverter)
PER
Permanent faults
WARN
Warnings
BDCF
Faults of battery charge/discharge circuit
BDCPF
Permanent faults of battery charge/discharge circuit
BATW
Battery warnings
BATP
Battery protection
BATF1
Battery faults
BATF2
Viewing the Error Record
Press / to turn pages and view all error
records.
1: the error is triggered.
0: the error is cleared.
Error Record
18022708:55:27 010 0
P1/1
18022707:11:21 501 1
10.8 Auto Test (Italy)
The inverter is integrated with interface protection functions and provides an
auto test system to verify the maximum / minimum frequency and maximum /
minimum voltage functions. The Auto Test item can only display when the
country code is set to IT (Italy), so the screenshots introduced in this section
will be in Italian.
Press ENT to confirm
Iniziare Autotest and
start the auto test.
Menu
Auto Test
3/3
Iniziare Autotest
Auto Test
Canc. Guasto Test
If the inverter is in the status of Error or
Turn off, it cannot start the test and a
prompt interface will appear.
During normal auto testing, the LCD will
automatically cycle through the grid
protection testing items.
Non è possibile
di avviare in caso
di guasto e tasto
di spegnimento!