2 System Solution
The inverter must only be operated with PV strings of protection class
II in accordance with IEC 61730, application class A. It is not permitted
for the positive pole or the negative pole of the PV strings to be
grounded. This can cause the inverter to be destroyed.
Damages to the product due to a faulty or damaged PV installation are
not covered by warranty.
Any use other than that described in this document is not permitted.
For the TT utility grid, the N line voltage to ground must be 30 V or less.
SH3K6/SH4K6 is a single-phase hybrid inverter applicable to on-grid PV
systems. With the integrated Energy Management System (EMS), it can control
and optimize the energy flow in order to increase the self-consumption of the
system.
Inverter
The type description is as follows:
SH 3K6
Code of power level
Code of Sungrow hybrid inverter
Tab. 2-1 Power Level Description
Type
Nominal Output Power
Nominal Grid Voltage
SH3K6
3680 W
230 Vac (single phase)
SH4K6
4600 W