User Manual 10 Appendix II: LCD Operation
85
When the grid voltage or frequency
reaches the recovery value, the
corresponding error code displayed on
the LCD will be cleared and the
inverter can start operating.
Vmax-recover
Vmin-recover
253.0V
195.5V
Fmax-recover
Fmin-recover
51.50Hz
47.50Hz
Power Ramp Rate (for countries except Great Britain):
The ramp up/down rate of power variation.
The power rate limit mode is enabled (ON) by default.
Set to OFF to turn off the function.
Power Ramp Rate En.
[ ON ]
010.00%
Power Ramp Rate
10-minute over-voltage protection (for countries except
Great Britain and Netherlands):
The inverter will automatically disconnect from the grid
within 3 s when the average voltage for a 10 min period
exceeds the set-point of 10-min Over Vtg.
Set to OFF to turn off the function.
10-min Over Vtg
253.0V
10-min Over Vtg En.
[ ON ]
Tab. 10-2 Protective Parameter Explanations
Recovery value for over-voltage fault. Inverter can start
operating only when the grid voltage is below this value.
Recovery value for under-voltage fault. Inverter can start
operating only when the grid voltage is above this value.
Recovery value for over-frequency fault. Inverter can start
operating only when the grid frequency is below this value.
Recovery value for under-frequency fault. Inverter can start
operating only when the grid frequency is above this value.
The ramp rate of power variation.
Over-voltage protection value of 10-min average voltage
10.4.7 Setting Reactive Power Regulation
For the modes Qt, Q(P) and Q(U), see “11 Appendix
IV: Power Response”.
The PF ranges from 0.8 leading to 0.8 lagging.
Leading: the inverter is sourcing reactive power to the
grid
Lagging: the inverter is sinking reactive power from the
grid.
Reactive Power
PF
OFF
Q(U)
Q(P)
Qt
PF Setting
PF + 1.000
+ : Lagging & - : Leading