User Manual 6 Electrical Connection
39
(Cross-section: 10 mm
2
to 25 mm
2
)
L1(A)
L2(B)
L3(C)
N
SET
21 22 17 18 19 20
L1 L1′ L2 L2′ L3 L3′ N
Grid
side
Load
side
The line conductor L1 supplies power to the Energy Meter. At least
the line conductor L1 and the neutral conductor must be connected
to the Energy Meter.
Just connect the line conductors L1, L1’ and the neutral conductor,
then the three-phase Energy Meter can be used as a single-phase
Energy Meter.
For Single-phase Energy Meter
1. Take out the Energy Meter (with 1-phase sensor) and the cables from the
packaging.
L
N
B
A
B2
A2
Power supply cable RS485 cable
2. Connect the cables to the Energy Meter.
Make sure that the 1-phase sensor is installed in the right direction: the
arrow on the sensor must point away from the grid towards the load.