NO. SH5.0/6.0RT SH8.0/10RT
①
40A/600V DC breaker *
②
25A/400V AC breaker 32A/400V AC breaker
③
25A/400V AC breaker
④
Depends on loads
⑤
Depends on household loads and inverter capacity (Optional)
⑥⑦
30mA RCD (Recommended)
⑧
300mA RCD (Recommended)
Note: * If the battery is integrated with a readily accessible internal DC breaker, no additional
DC breaker is required.
Note: The values in the table are recommended values and can be set to other values ac-
cording to actual conditions.
In the TT system, the following diagram is an example for grid systems without special re-
quirement on wiring connection.
NO. SH5.0/6.0RT SH8.0/10RT
①
40A/600V DC breaker *
②
25A/400V AC breaker 32A/400V AC breaker
③
25A/400V AC breaker
④
Depends on loads
⑤
Depends on household loads and inverter capacity
⑥⑦
30mA RCD (Recommended)
⑧
300mA RCD (Recommended)
Note: * If the battery is integrated with a readily accessible internal DC breaker, no additional
DC breaker is required.
Note: The values in the table are recommended values and can be set to other values ac-
cording to actual conditions.