097-58001-01 Revision E – September 2006 TimeProvider TL1 Reference Guide 69
Chapter 2 TL1 Command Syntax and Description
Operate Alarm Cutoff (OPR-ACO-ALL)
Operate Alarm Cutoff (OPR-ACO-ALL)
This command deactivates (opens) the minor, major, and critical audible alarm
relays.
This command has a default access level of USER.
Syntax
OPR-ACO-ALL:[<tid>]::[<ctag>];
Example
To deactivate the audible alarm relays:
Input
OPR-ACO-ALL:::TP1000;
Normal Response
TP-SSU
05-02-10 13:35:56
M TP1000 COMPLD
;
Autonomous Message
TP-SSU
05-02-10 13:35:56
A 2564 REPT EVT
"IMC,EQPT:ACO,TC,05-02-10,13-35-56,,,,:\"AUDIO ALARM IS DEACTIVATED\""
;
Note: When you deactivate the audible alarm relays using this
command, they reactivate when subsequent alarms occur.