Group 07: Start /Stop Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
07-00
Momentary Power Loss/ Fault
Restart Selection
0: Disable
0 - O O O
1: Enable
07-01 Fault Auto-Restart Time 0~7200 0 s O O O
07-02
Number of Fault Auto-Restart
Attempts
0~10 0 - O O O
07-03 Reserved
07-04 Direct Start at Power on
0: When the external run command
is enabled, direct start at power
up
1 - O O O
1: When the external run command
is enabled, unable to direct start
at power-up.
07-05
Automatic start delay at
power up
1.0~300.0
3.5 Sec
O O O
07-06
DC Injection Braking Start
Frequency
0.0~10.0 0.5 Hz O O O
07-07 DC Injection Braking Current 0~100 50 % O O O
07-08
DC Injection Braking Time at
Stop
0.00~10.00 0.50 s O O O
07-09 Stop Mode Selection
0: Deceleration to Stop
0 -
O O O
1: Coast to Stop O O O
2: DC Braking Stop O O X
3: Coast to Stop with Timer O O O
07-10
~
07-12
Reserved
07-13 Low Voltage Detection Level
200V: 150~300 190
V O O O
400V: 300~600 380
07-14 Pre-excitation Time 0.00~10.00 2.00 s X O X
07-15 Pre-excitation Level 50~200 100 % X O X *6
07-16
DC Injection Braking Time at
Start
0.00~100.00 0.00 s O O O
07-17 Reserved
07-18 Minimum Base block Time 0.1~5.0 - Sec O O O
07-19
Direction-Detection Speed
Search Operating Current
0~100 50 % O O X
07-20
Speed Search Operating
Current
0~100 20 % O O X
07-21
Integral Time of Speed
Searching
0.1~10.0 2.0 Sec O O X
07-22
Delay Time of Speed
Searching
0.0~20.0 0.2 Sec O O X
07-23 Voltage Recovery Time 0.1~5.0 2.0 Sec O O X
07-24
Direction-Detection Speed
Search Selection
0: Disable
1 - O O X
1: Enable
07-25 Low voltage Detection Time 0.00~1.00 0.02 Sec O O O