2: Timer Function
Symbol Description
Timer mode (0-7)
Timing unit:
1:0.0~999.9 second
2:0~9999 second
3:0~9999 minute
Use (I1~f8) to reset timing value
ON: Internal timing value is reset and timer output is OFF
OFF: Internal timer stays running
Internal timer value
Timer set value (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8,constant)
Timer output (T1 to T8, there are a total of 8 timers)
Timer mode description
Example:
[T5]
T5
000.0
010.0
1
1
I1
[Q1]
When I1=ON, the 5th timer
starts
T5
When th e time reaches th e
set value of 10.0 seconds,
output T5 is turned ON.
Input under function Program Mode
Input from the Ladder Program
Timer set value Present timing value
Timing unit is 0.1 secon d Timer Mode1