4-323
4.6.2 Register and Data Format
Command Data (Read / Write)
Register No. Bit Content
2500H Reserved
2501H
Operation Signal
0 Operation Command 1 : Run 0 : Stop
1
Reverse Command 1 : Reverse 0 : Forward
2
External Fault 1 : Fault
3
Fault Reset 1 : Reset
4 Reserved
5 Reserved
6 Multi-function Comm S1 1 :“ON”
7 Multi-function Comm S2 1 :“ON”
8 Multi-function Comm S3 1 :“ON”
9 Multi-function Comm S4 1 :“ON”
A Multi-function Comm S5 1 :“ON”
B Multi-function Comm S6 1 :“ON”
C Reserved
D Reserved
E Controller Mode 1 : “ON”
F Reserved
2502H Frequency Command (Unit: 0.01Hz)
2503H Reserved
2504H Speed Limit (+/- 120 correspond to +/-120%)
2505H AO1 (0 ~ 1000): Voltage (0.00V ~ 10.00V); Current (4mA~20mA)
2506H AO2 (0 ~ 1000): Voltage (0.00~10.00V); Current (4mA~20mA)
2507H DO
2508H Reserved
2509H Reserved
250AH Reserved
250BH Reserved
250CH Reserved
250DH Reserved
250EH Reserved
250FH Reserved
2510H G12-00 H-WORD
2511H G12-00 L-WORD
Note: Write a zero into the register for not used bit; do not write data to a reserved register.