8-6
8.5 Emergency Stop
The emergency stop time is used in combination with multi-function digital input function #14
(Emergency stop). When emergency stop input is activated the inverter will decelerate to a stop using
the Emergency stop time (00-26) and display the [EM STOP] condition on the keypad.
Note: To cancel the emergency stop condition the run command has to be removed and emergency stop input
deactivated.
Example: Emergency Stop Switch set for input terminal S5 (03-04 = 14).
(S+) (S-) S1 S3
S5
24V +10V MT GND GND AI1 AI2
E24VG
S2 S4 S6 F1 F2 PO PI AO1 AO2
E
Emergency
Stop Switch
Connect shield
to control
ground
terminal
Emergency Stop
Common/
24VG
Control Terminals /
User Terminals
00-26 Emergency stop time
Range
0.1~6000.0 Sec