8-8
8.7 Analog Output Setup
Signal: Use parameter 04-11 to select the analog output signal for AO1 and parameter 04-16 to select
the analog output signal for AO2.
Gain: Use parameter 04-12 to adjust the gain for AO1 and parameter 04-17 to adjust the gain for AO2.
Adjust the gain so that the analog output (10V/20mA) matches 100% of the selected analog output
signal (04-11 for AO1 and 04-16 for AO2).
Bias: Use parameter 04-13 to adjust the bias for AO1 and parameter 04-18 to adjust the bias for AO2.
Adjust the bias so that the analog output (0V/4mA) matches 0% of the selected analog output signal
(04-11 for AO1 and 04-16 for AO2).
Example: Analog Output 1 Wiring
(S+) (S-) S1 S3 S5 24V +10V MT
GND
GND
AI1 AI2
24VG S2 S4 F1 F2 PO PI
AO1
AO2
E
Connect shield
to control
ground terminal
Common/
GND
Control Terminals /
User Terminals
S6
Analog
Output 1
+
-
E
04-11 AO1 function Setting
Range
0: Output frequency
1: Frequency command
2: Output voltage
3: DC voltage
4: Output current
5: Output power
6: Motor speed
7: Output power factor
8: AI1 input
9: AI2 input
10: Torque command
11: q -axis current
12: d-axis current
13: Speed deviation
14: Reserved
15: ASR output
16: Reserved
17: q-axis voltage
18: d-axis voltage
19~20: Reserved
21: PID input
22: PID output
23: PID target value
24: PID feedback value
25: Output frequency of the soft starter
26~27: Reserved
28: Communication control