6-1
Chapter 6 Speed Reference Command Configuration
The inverter offers users several choices to set the speed reference source. The most commonly used
methods are described in the next sections.
Frequency reference command is selected with parameter 00-05.
00-05: Main Frequency Command (Frequency Source)
This function sets the frequency command source.
Setting Range: 0 to 5
To set parameter 00-05:
- After power-up press the DSP/FUN key
- Select 00 Basic Fun
- Press READ/ ENTER key
- Select parameter -05 with the UP/DOWN and keys and press the READ/ ENTER key.
In the parameter list move cursor to 00-05 with the UP/DOWN keys and press READ/ ENTER key to
select.
00-05 Main Frequency Command Source Selection
Range
0: Keypad
1: External Terminal (Analog AI1)
2: Terminal Command UP / DOWN
3: Communication control (RS-485)
4: Reserved
5: Reserved
6: RTC
7: AI2 Auxiliary Frequency
6.1 Reference from Keypad
Speed reference from the keypad is the default setting. Press the READ/ ENTER key first and use the
</RESET, and keys to change the speed reference.