EasyManua.ls Logo

TECO F510 series - 11.9.7 Meanings of each character

TECO F510 series
555 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11-24
11.9.7 Meanings of each character
Control character
Bit
Description 1 0
0
Operation command Operate Stop
1
Reverse command Reverse Forward
2
External error Error -
3
Error reset Reset -
4~5
Reserved - -
6
Multi-function terminal S1 ON OFF
7
Multi-function terminal S2 ON OFF
8
Multi-function terminal S3 ON OFF
9
Multi-function terminal S4 ON OFF
A
Multi-function terminal S5 ON OFF
B
Multi-function terminal S6 ON OFF
C
Multi-function terminal S7 ON OFF
D
Multi-function terminal S8 ON OFF
E
Controller mode ON OFF
F
Communication setting torque command ON
Status character
Bit Meaning 1 0
0
Operation status Operate Stop
1
Direction status Reverse Forward
2
Frequency converter operation preparation
status
Preparation
complete
Not yet
prepared
3
Error Abnormal Normal
4
Warning ON OFF
5
Zero speed ON OFF
6
Model 440 ON OFF
7
Frequency reached ON OFF
8
Any frequency reached ON OFF
9
Frequency detection one ON OFF
A
Frequency detection two ON OFF
B
Low voltage ON OFF
C
Frequency converter no output ON OFF
D
Frequency not according to communication ON OFF
E
SeqNotFromComm ON OFF
F
Over-torque ON OFF

Table of Contents

Other manuals for TECO F510 series

Related product manuals