3-1
Chapter 3 Environment and Installation
3.1 Environment
The environment will directly affect the proper operation and the life span of the inverter. To
ensure that the inverter will give maximum service life, please comply with the following
environmental conditions:
Protection
Protection
Class
IP20/ IP21/ NEMA 1, IP00
IP55/ NEMA 12
Ambient Environment
Operating
Temperature
IP20/IP21/IP55: -10°C - +40°C (14 -104 °F)
IP00 (Without Cover): -10°C - +50°C (14-122 °F)
Enhanced type frame 5 is 50°C without de-rating.
The maximum operating temperature is 60°C,
but it is required to derate 2% of current
at each additional 1
°C.
If several inverters are placed in the same control panel, provide a heat removal means to
maintain ambient temperatures
Storage
Temperature
-20°C - +70°C (-4 -158 °F)
Humidity
95% non-condensing
Relative humidity 5% to 95%, free of moisture.
(Follow IEC60068-2-78 standard)
Altitude
Altitude: Below 1000 m (3281 ft.)
It is required to derate 1% of current at each additional 100 m.
The maximum altitude is 3000 m.
Installation
Site
Avoid direct sunlight.
Avoid exposure to rain or moisture.
Avoid oil mist and salinity.
Avoid corrosive liquid and gas.
Avoid dust, lint fibers, and small metal filings.
Avoid electromagnetic interference (soldering machines, power machines).
Keep away from radioactive and flammable materials.
Avoid vibration (stamping, punching machines etc.).
Add a vibration-proof pad if the situation cannot be avoided.
Shock
Maximum acceleration: 1.2G (12m/s²), from 49.84 to 150 Hz
Displacement amplitude : 0.3mm (peak value), from 10 to 49.84 Hz
(Follow IEC60068-2-6 standard)