11.3 Input Noise Filters
A. Input Noise Filter on Specifications & Ratings
Install a noise filter on power supply side to eliminate noise transmitted between the power line and the
inverter. The inverter noise filter shown in Table 11.3.1 and Table 11.3.2 below meets the EN61800-3
class A specification. 400V inverter class models can be ordered with integrated noise filter.
Table 11.3.1 Input Noise Filter Specifications and Ratings (IP20)
Inverter size Noise filter
Input voltage HP Model Dimension
1

200V
1HP/2HP/3HP FN3258-30-47 240*50*85
3
200V
1HP/2HP/3HP FN3258-16-45 264*45*70
5HP/7.5HP FS32124-23-99 290*50*85
10HP/15HP FS32123-40-99 330*85*90
20HP FS32125-56-99 318*80*135
25HP/30HP FS32125-79-99 360*95*90
40HP/50HP FS32125-138-99 320*226.5*86
60HP/75HP FS32125-211-99 320*226.5*86
100HP/125HP FS32125-312-99 320*226.5*86
150HP/175HP FN3270H-1000-99 610*230*132
3
400V
1HP/2HP/3HP JN5-FLT-8A-02 102*130*92
5HP/7.5HP/10HP JN5-FLT-19A 123*141*92
15HP/20HP JN5-FLT-33A 132*206*124
25HP/30HP/40HP JN5-FLT-63A 127*260*131
50HP/60HP/75HP JN5-FLT-112A 186*284*128
100HP/125HP FS32126-165-99 320*226.5*86
150HP/175HP/215HP/250HP FS32126-361-99 320*226.5*86
300HP/375HP/425HP FN3270H-1000-99 610*230*132
535HP/670HP/800HP FN3270H-1000-99 610*230*132
B. Input or Output Noise Filter (EMI Suppression Zero Phase Core)
- Part Number: 4H000D0250001
- Select a matched ferrite core to suppress EMI noise according to the required power rating and wire
size.
- The ferrite core can attenuate high frequencies in the range of 100 kHz to 50 MHz, as shown in figure
11.4.1 below, and therefore should minimize the RFI generated by the inverter.
- The zero-sequence noise ferrite core can be installed either on the input side or on the output side. The
wire around the core for each phase should be wound by following the same convention and in one
direction. The more turns without resulting in saturation the better the attenuation. If the wire size is too
large to be wound, all the wiring can be grouped and put through several cores together in one direction.

Table of Contents

Other manuals for TECO F510 series

Related product manuals