Do not check signals on circuit boards while the inverter is running.
1.6 Maintenance, Inspection and Replacement
Warning
Wait a minimum of 5 minutes after power has been turned OFF before starting an
inspection. Also confirm that the charge light is OFF and that the DC bus voltage has
dropped below 25Vdc. Wait a minimum of 15 minutes while inverter is over 20HP.
Never touch high voltage terminals in the inverter.
Make sure power to the inverter is disconnected before disassembling the inverter.
Only authorized personnel should perform maintenance, inspection, and replacement
operations. (Take off metal jewelry such as watches and rings and use insulated tools.)
Caution
The Inverter can be used in an environment with a temperature range from 14° -104°F
(-10-40°C) and relative humidity of 95% non-condensing.
The inverter must be operated in a dust, gas, mist and moisture free environment.
1.7 Disposal of the Inverter
Caution
Please dispose of this unit with care as an industrial waste and according to your required
local regulations.
The capacitors of inverter main circuit and printed circuit board are considered as
hazardous waste and must not be burned.
The Plastic enclosure and parts of the inverter such as the top cover board will release
harmful gases if burned.
Equipment containing electrical components may not be disposed of together with
domestic waste. It must be separately collected with electrical and electronic waste
according to local and currently valid legislation.