3-2
3.2 Installation
3.2.1 Installation Spaces
When installing the inverter, ensure that inverter is installed in upright position (vertical
direction) and there is adequate space around the unit to allow normal heat dissipation as per
the following Fig. 3.2.1
5.9in.
150mm
5.9in.
150mm
Air Flow
5.9in.
150mm
X
5.9in.
150mm
X
Fig 3.2.1: F510 Installation space
X = 1.18” (30mm) for inverter ratings up to 18.5kW
X = 1.96” (50mm) for inverter ratings 22kW or higher
Important Note: The inverter heatsink temperature can reach up to 90°C/ 194°F during
operation; make sure to use insulation material rated for this temperature.