10.5 PM Motor Auto-tuning Error
When a fault occurs during auto-tuning of a PM motor, the display will show the “IPErr” fault and the
motor stops. The fault information is displayed in parameter 22-22.
Note: The fault contact output does not energize with an auto-tuning fault. Refer to Table 10.5.1, for fault
information during tuning, cause and corrective action.
Table 10.5.1 Auto-tuning fault and corrective actions for PM motor
Error Description Cause Corrective action
01
Magnetic pole alignment
tuning failure (static).
Inverter output current
does not match motor
current.
Check the motor tuning
data (22-02).
Check inverter capacity
02~04
Reserved
05 Circuit tuning time out.
System abnormality during
circuit tuning.
Check for active
protection functions
preventing auto-tuning.
06
Reserved
07 Other motor tuning errors. Other tuning errors.
Check the motor tuning
data (22-02).
Check motor connection.
08
Reserved
09
Current out of range during
circuit tuning.
Inverter output current
does not match motor
current.
Check the motor tuning
data (22-02).
Check inverter capacity
10 Reserved
11
Parameter tuning and
detecting time out.
Error relationship between
voltage and current.
Check if the setting value
of parameter 22-11 is too
low, but its value cannot
exceed 100% of the
inverter.
Check motor connection.