EasyManua.ls Logo

TECO F510 series - Power Input Wire Size, NFB and MCB Part Numbers

TECO F510 series
555 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-50
Power Input Wire Size, NFB and MCB Part Numbers
The following table shows the recommended wire size, molded case circuit breakers and magnetic
contactors for each of the F510 models. It depends on the application whether or not to install a
circuit breaker. The NFB must be installed between the input power supply and the inverter input
(R/L1, S/L2, T/L3).
Note: When using a ground protection, make sure the current setting is above 200mA and trip delay time
is 0.1 sec of higher.
Table 3.3.6.3 Wiring Instrument for 200V400V class (IP00/IP20 type)
F510 Model Wire size (mm
2
)
NFB
*3
MC
*3
Power
supply
Horse power
(HP)
Rated
KVA
Rated
current (A)
Main
circuit
*1
Grounding
E(G)
Control
line
*2
200V
1 Ø3Ø
1HP 1.9 5
25.5 25.5 0.52
TO-50EC(15A) CU-11
2HP 2.9 7.5
25.5 3.55.5 0.52
TO-50EC(20A) CU-11
3HP 4.0 10.6
3.55.5 3.55.5 0.52
TO-50EC(30A) CU-11
200V
3 Ø
5HP 5.5 14.5
3.55.5 3.55.5 0.52
TO-50EC(30A) CU-16
7.5HP 8.0 22 5.5 5.5
0.52
TO-50EC(30A) CU-16
10HP 11.4 30 8
5.58 0.52
TO-100EC(50A) CU-18
15HP 15 42 8
5.58 0.52
TO-100EC(50A) CU-27
20HP 21 56 14 8
0.52
TO-100EC(100A) CU-50
25HP 26 69 22 8
0.52
TO-100EC(100A) CU-65
30HP 30 80 22 14
0.52
TO-225E(125A) CU-80
40HP 42 110 38 14
0.52
TO-225E(150A) CN-100R
50HP 53 138 60 22
0.52
TO-225E(175A) CN-125R
60HP 64 169 80 22
0.52
TO-225E(200A) CN-150
75HP 76 200 100 22
0.52
TO-225E(225A) CN-180
100HP 95 250 150 22
0.52
TO-400S(300A) CN-300
125HP 119 312 200 38
0.52
TO-400S(400A) CN-300
150HP 137 400 300 38
0.52
TO-600S(600A) CN-400
175HP 172 450 250*2P 50
0.52
TO-800S(800A) CN-630
400V
3 Ø
1HP 2.6 3.4
25.5 25.5 0.52
TO-50EC(15A) CU-11
2HP 3.1 4.1
25.5 3.55.5 0.52
TO-50EC(15A) CU-11
3HP 4.1 5.4
25.5 3.55.5 0.52
TO-50EC(15A) CU-11
5HP 7.0 9.2
25.5 3.55.5 0.52
TO-50EC(15A) CU-18
7.5HP 8.5 12.1
25.5 3.55.5 0.52
TO-50EC(15A) CU-18
10HP 13.3 17.5
35.5 3.55.5 0.52
TO-50EC(20A) CU-18
15HP 18 23 5.5 5.5
0.52
TO-50EC(30A) CU-25
20HP 24 31 8 8
0.52
TO-100EC(50A) CU-25
25HP 29 38 8 8
0.52
TO-100EC(50A) CU-35
30HP 34 44 8 8
0.52
TO-100EC(50A) CU-50
40HP 41 58 14 8
0.52
TO-100EC(75A) CU-50
50HP 55 73 22 8
0.52
TO-100EC(100A) CU-65
60HP 67 88 22 14
0.52
TO-100EC(100A) CN-80
75HP 79 103 38 14
0.52
TO-225E(150A) CN-100R
100HP 111 145 60 22
0.52
TO-225E(175A) CN-150
125HP 126 168 80 22
0.52
TO-225E(225A) CN-150
150HP 159 208 150 22
0.52
TO-400S(300A) CN-300
175HP 191 250 150 22
0.52
TO-400S(300A) CN-300
215HP 226 296 200 30
0.52
TO-400S(400A) CN-300
250HP 250 328 250 30
0.52
TO-400S(400A) CN-400
300HP 332 435 300 38
0.52
TO-600S(600A) CN-630
375HP 393 515 250*2P 50
0.52
TO-800S(800A) CN-630

Table of Contents