4-49
Group 12: Monitoring Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
12-39 PID Feedback
Display the feedback value of the
PID controller
(100% corresponds to the
maximum frequency set by 01-02
or 01-16)
- % O O O
12-40 Reserved
12-41 Heatsink Temperature
Display the heatsink temperature
of IGBT temperature.
-
℃
O O O
12-42 RS-485 Error Code
LCD Display:
0000 0000
1: CRC Error
1: Data length Error
1: Data Function Error
1: Parity Error
1: Overrun Error
1: Framing Error
1: Time Out Error
Reserved
LED Display: (without any error)
LED Display: (with certain error)
1: CRC Error
1: Data length Error
1: Data Function Error
1: Parity Error
1: Framing Error
1: Time out Error
Reserved
1: Overrun Error
- - O O O *7
12-43 Inverter Status
LCD Display:
0000 0000
1: Inverter ready
1: During running
1: During zero speed
1: During speed agree
1: During fault detection
(minor fault)
1: During fault detection
(major fault)
Reserved
LED Display:
Inverter ready 1
Running 2
Zero Speed 4
Frequency Agree 8
Warning 16
Error 32
Inverter status display is the
summed up value. Ex: Display of
the value 6 means the inverter is
running in zero speed.
101B - O O O