Group 12: Monitoring Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
12-22 Motor’s Rotation Speed
Display motor’s current rotation
speed
in VF/SLV mode
Motor’s rotation speed = output
power x(120/motor’s pole number)
In PG/SV mode, motor’s rotation
speed is calculated by feedback
frequency.
Max limit is 65535
- rpm O O O
12-23 Output Power Factor
Display the current output power
factor
- - O O O
12-24 Control Mode
Display control mode
0 : VF
2 : SLV
5 : PM SLV
- - O O O
12-25 AI1 Input
Display the current Al1 input
(0V corresponds to 0%, 10V
corresponds to 100%,)
- % O O O
12-26 AI2 Input
Display the current Al2 input
(0V or 4mA corresponds to 0%,
10V or 20mA corresponds to
100%)
- % O O O
12-27 Motor Torque
Display the current torque
command
(100% corresponds to motor
torque )
- % X O O
12-28 Motor Torque Current (Iq) Display the current q-axis current - % X O O
12-29 Motor Excitation Current (Id) Display the current d-axis current - % X O O
12-30
~
12-35
Reserved
12-36 PID Input
Display input error of the PID
controller (PID target value - PID
feedback)
(100% corresponds to the
maximum frequency set by 01-02
or 01-16)
- % O O O
12-37 PID Output
Display output of the PID controller
(100% corresponds to the
maximum frequency set by 01-02
or 01-16)
- % O O O
12-38 PID Setting
Display the target value of the PID
controller
(100% corresponds to the
maximum frequency set by 01-02
or 01-16)
- % O O O