8-9
04-12 AO1 gain value
Range
0.0~1000.0%
04-13 AO1 bias-voltage value
Range
-100.0~100.0%
04-16 AO2 function Setting
Range
See parameter 04-11
04-17 AO2 gain value
Range
0.0~1000.0%
04-18 AO2 bias-voltage value
Range
-100.0~100.0%
04-19 AO2 Output Signal Type
Range
0: AO1:0~10V AO2:0~10V
1: AO1:0~10V AO2:4~20mA
2: AO1:4~20mA AO2:0~10V
3: AO1:4~20mA AO2: 4~20mA
04-20 Filter Time of AO Signal Scan
Range
0.00~0.50s
Monitor Signal
100%
0%
Analog Output Signal
10V(or 20mA) × Gain
(20mA) 10V
-10V
(-10V) × Gain
(4mA) 0V
{
Bias
{
Bias
Analog output level adjustment