4-67
Group 23 Pump & HVAC Function Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
23-48
Maximum Flow Value of
Feedback
0.01 ~ 99.00 80.00 % O O O
23-49
Maximum Flow Warning Time
of Feedback
0.0 ~ 255.0 3.0 Sec O O O
23-50
Maximum Flow Stop Time of
Feedback
0.0 ~ 255.0 6.0 Sec O O O
23-51
Minimum Flow Value of
Feedback
0.01 ~ 99.00 10.00 % O O O
23-52
Minimum Flow Warning Time
of Feedback
0.0 ~ 255.0 3.0 Sec O O O
23-53
Minimum Flow Stop Time of
Feedback
0.0 ~ 255.0 6.0 Sec O O O
23-54
Detection Function of Low
Suction
0: Disable
0 O O O
1: PID Error Value
2: Current
3: Current and PID Error Value
23-55 Detection Time of Low Suction 0 ~ 30.0 10.0 Sec O O O
23-56 PID Error Level of Low Suction 0 ~ 30 10 % O O O
23-57
Current Level of Low
Suction(Motor Rated Current)
0 ~ 100 10 % O O O
23-58 Reaction of Low Suction
0: Disable
0 O O O
1: Warning
2: Fault
3: Fault & Restart
23-59
Source of HVAC Pressure
Command
0: Set by 23-47
0 O O O
1: Set by AI
23-60 HVAC Unit Display
0: GPM
0 O O O
Note4
1: FPM
2: CFM
3: GPH
23-66 Derating of Current Level 10~200 110 % O X X
23-67 Derating of Delay Time 1.0~20.0 10.0 Sec O X X
23-68 Derating of Frequency Gain 1~100 90 % O X X
23-69 OL4 Current Level 10~200 120 % O X X
23-70 OL4 Delay Time 0~20.0 5.0 Sec O X X
23-71 Maximum Pressure Setting 0.10~650.00 10.00 PSI O O O
Note3
23-72
Switching Time of Alternation
in Parallel
0: Hour
0 O O O
Note4
1: Minute
23-73 Slave Wake-up Selection
0: Disable
0
O O O
Note4
1: Enable
23-74 High Pressure Setting
0: Disable
2 O O O
Note5
1: High Pressure Warning
2: High Pressure Warning or Error
23-75 Low Pressure Setting
0: Disable
0 O O O
Note5
1: Low Pressure Warning
2: Low Pressure Warning or Error