4-69
Group 24 Pump Control Function Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
xx1xb: Relay 2 Enable
x0xxb: Relay 3 Disable
x1xxb: Relay 3 Enable
0xxxb: Relay 4 Disable
1xxxb: Relay 4 Enable
24-02 Selection of Relay 5-8 Function
xxx0b: Relay 5 Disable
0000b O O O
xxx1b: Relay 5 Enable
xx0xb: Relay 6 Disable
xx1xb: Relay 6 Enable
x0xxb: Relay 7 Disable
x1xxb: Relay 7 Enable
0xxxb: Relay 8 Disable
1xxxb: Relay 8 Enable
24-03
Duration of Upper Limit
Frequency
1.0 ~ 600.0 300.0 Sec O O O *1
24-04
Duration of Lower Limit
Frequency
1.0 ~ 600.0 300.0 Sec O O O *1
24-05
Switching Time of Magnetic
Contactor
0.1 ~ 20.0 1.00 Sec O O O *1
24-06 Allowable Bias of Pump Switch 0.0 ~ 20.0 0.0 % O O O *1
24-07 Pump Control Source Selection
0: 1 to 8 pump card
0 O O O
1: Built-in 1 to 3 control mode
24-08 Relay Switching Time 0~240 1
Hr/
min
O O O
Note1
24-09 Frequency/ Target Switch
0: Disable
1: Enable
0 O O O
Note3
24-10
Stop Mode Selection on Mode
6/7/9
0: Disable
1: Enable
0 O O O
Note3
24-11
High Pressure Limit Level 0~10000 500 - O O O
Note4
24-12
Delay Time of High Pressure
Warning
0.0 ~ 600.0 10.0 Sec O O O
Note4
24-13
Delay Time of High Pressure
Error
0.0 ~ 600.0 20.0 Sec O O O
Note4
24-14
Low Pressure Limit Level
0~10000 0 - O O O
Note4
24-15
Delay Time of Low Pressure
Warning
0.0 ~ 600.0 0.0 Sec O O O
Note4
24-16
Delay Time of Low Pressure
Error
0.0 ~ 600.0 0.0 Sec O O O
Note4
24-17
PID Control during Increasing/
Decreasing pumps
0: PID Control is disabled during
increasing/ decreasing pumps
0 - O O O
Note6
1: PID Control is enabled during
increasing/ decreasing pumps