4-72
■ 3-wire operation
For 3-wire operation set any of parameters 03-02 to 03-05 (terminal S3 ~ S6) to 26 to enable 3-wire
operation in combination with S1 and S2 terminals set to operation command and stop command.
Parameter 13-08 for 3-wire program initialization, multi-function input terminal S1 is set to run operation,
S2 for stop operation and S5 for forward/reverse command. (Additionally must be 00-02=1, 11-00=0)
Note: Terminal S1 must be closed for a minimum of 50ms to activate operation.
Figure 4.4.2 Wiring example of 3-wire
Figure 4.4.3 Timing chart of 3-wire operation