4-74
00- 04 Language Selection (for LCD only)
Range
【0】:
English
【1】: Simple Chinese
【2】: Traditional Chinese
【3】: Turkish
It is only for LCD keypad to select. This parameter is not allowed to be modified when 13-08 (restore
factory setting) is active but it is still initialized in inverter software V1.3).
00-04 = 0: English Display
00-04 = 1: Simple Chinese Display
00-04 = 2: Traditional Chinese Display
00-04 = 3: Turkish Display
00- 05
Main Frequency Command Source Selection
00- 06
Alternative Frequency Source Selection
Range
【0】:
Keypad
【1】:
External control (analog AI1)
【2】:
Terminal UP / DOWN
【3】:
Communication control
【4】:
Reserved
【5】: Reserved
【6】:
RTC
【7】:
AI2 Auxiliary frequency
00-05/00-06= 0: Keypad
Use the keypad to enter the frequency reference or by setting parameter 05-01 (frequency reference 1).
Note that once the frequency command is switched to alternative one, and 00-06=0, the frequency just can
be adjusted via parameter 05-01. Refer to section 4.1.4 for details.
00-05/00-06= 1: External control (Analog Input)
When 04-05=0, give frequency reference command from control circuit terminal AI1 (voltage input). If
auxiliary frequency is used, refer to the descriptions of multi-speed functions in parameter 03-00~05.
When frequency reference command is control by either AI1 or AI2, please regard the following setting:
00-05/ 00-06 are set individually to be 1 and 7.
Set AI2 signal type in 04-00 (AI1 is always 0~10V).
Set 04-05=0 (Auxiliary frequency setting).
Set multi-function terminal function of 03-00~05 to be 13, then frequency reference command can be
switched to AI1 control or AI2 control.
When 04-05=1, give frequency reference command from control circuit terminal AI1 (voltage input) or AI2
(current input, set by 04-00).
Use AI1 terminal when voltage input signal is the main frequency reference command.
Use AI2 terminal when current input signal (4-20mA) is the main frequency reference command.
Use analog reference from analog input AI1 or AI2 to set the frequency reference (as shown in Figure
4.4.4). Refer to parameter 04-00 to select the signal type.